Module Mounting Systems (MMS) are critical structural components that securely hold solar PV modules in position. Ground-mounted systems are specialized structures designed to support PV arrays on land-based installations. This training module covers the complete process from site assessment to final installation, ensuring structural integrity and optimal system performance.
Training Duration: 1 week
Prerequisite Skills: Basic knowledge of structural components, materials, and construction tools
Ground mounting systems are primarily classified based on their foundation type, tracking capability, and structural configuration.
- Pile-driven systems: Metal piles driven directly into the ground.
- Concrete foundation systems: Precast or cast-in-place concrete foundations.
- Ballasted systems: Heavy weights (typically concrete blocks) secure the structure.
- Ground screw systems: Helical screws augered into the soil.
- Earth anchor systems: Tension-based anchoring mechanisms.
- Fixed-tilt systems: Modules set at a permanent angle.
- Single-axis tracking: Modules rotate on one axis (typically east to west).
- Dual-axis tracking: Modules rotate on two axes to maximize solar exposure.
- Seasonally adjustable systems: Manual tilt adjustment several times per year.
Design Consideration: System selection should balance initial cost, expected energy yield, maintenance requirements, and site conditions. Fixed systems are more economical but produce less energy than tracking systems.
- Total Station or GPS equipment.
- Soil testing equipment (penetrometer, soil sampler).
- Measuring tape (30m & 5m).
- Marking equipment (flags, stakes, spray paint).
- Site plans and structural drawings.
- Drone for aerial site mapping (optional).
- Inclinometer for slope measurements.
- Identify and map site boundaries.
- Measure and document elevation changes.
- Calculate slope percentages across the site.
- Identify water drainage patterns.
- Document any obstructions (trees, rocks, utilities).
- Assess potential shading issues from nearby structures or vegetation.
- Create contour maps of the installation area.
Geotechnical assessment is crucial for determining the appropriate foundation system and structural requirements.
- Conduct soil borings at multiple locations across the site.
- Perform Standard Penetration Tests (SPT) as per IS 2131.
- Determine soil classification according to IS 1498.
- Test soil bearing capacity.
- Measure soil resistivity for grounding system design.
- Assess soil corrosivity for foundation material selection.
- Check for groundwater levels and seasonal variations.
Parameter |
Standard |
Requirement |
Wind Load |
IS 875 (Part 3) |
Calculate based on wind zone map of India |
Seismic Zone |
IS 1893 |
Design as per zone classification |
Snow Load |
IS 875 (Part 4) |
For high altitude locations |
Flood Risk |
Local data |
100-year flood level + safety margin |
Code Compliance: All structural designs must comply with IS 800:2007 for steel structures and IS 456:2000 for concrete elements.
- Remove vegetation, rocks, and debris from installation area.
- Identify and mark underground utilities.
- Clear an additional perimeter around array area (minimum 3m) for access.
- Preserve topsoil separately for later restoration if required.
- Document pre-construction site conditions with photographs.
- Grade the site to reduce slope to project specifications (typically <5-10%).
- Establish proper drainage patterns away from array areas.
- Compaction of soil to specified density (typically 95% of modified Proctor).
- Install erosion control measures as required by site conditions.
- Implement stormwater management features per approved plans.
Proper site access is critical for construction equipment and future maintenance.
- Create all-weather access roads of minimum 4m width.
- Ensure road base can support heavy construction equipment (crane, pile drivers).
- Install culverts or drainage crossings as needed.
- Provide turning radius adequate for delivery vehicles (minimum 15m).
- Create staging areas for materials and equipment.
Foundation selection depends on soil conditions, structural requirements, terrain, and project economics.
Foundation Type |
Suitable Soil Conditions |
Advantages |
Limitations |
Driven Piles |
Loam, clay, sand |
Quick installation, no concrete |
Not suitable for rocky soil |
Concrete Piers |
Most soil types |
High load capacity, stability |
Time-consuming, higher cost |
Ground Screws |
Soft to medium-hard soils |
Minimal site disturbance, removable |
Limited load capacity |
Ballasted System |
Flat terrain with stability |
No ground penetration, portable |
Requires more materials, higher weight |
- Mark pile locations as per approved drawings.
- Position pile driving equipment with proper alignment.
- Drive piles to specified depth (typically 1.5-3m).
- Conduct pull-out tests on sample piles (min. 1 test per 50 piles).
- Verify vertical and horizontal alignment (tolerance: ±10mm).
- Apply anti-corrosion treatment to exposed portions.
- Document installation depths and pull-out test results.
- Excavate foundation pits as per design (minimum 300mm below frost line).
- Place 75-100mm PCC (1:4:8) at the base.
- Install reinforcement cage as per structural drawings.
- Position anchor bolts or embedded parts with templates.
- Pour concrete (minimum M25 grade) with proper vibration.
- Cure concrete for minimum 7 days.
- Conduct core tests if required (1 sample per 50 foundations).
- Backfill and compact soil around foundations.
Quality Control: Foundation location accuracy is critical. Maximum deviation in position should not exceed ±20mm, and level deviation should not exceed ±5mm.
- Verify structural components against approved shop drawings.
- Check material test certificates for compliance with IS 2062.
- Inspect galvanization quality (minimum 80 microns as per IS 4759).
- Verify bolt grades (typically 8.8) and dimensions.
- Document material quality and quantity received.
- Store materials properly to prevent damage or galvanization deterioration.
- Align column base plates with foundation anchor bolts.
- Use leveling nuts for precise height adjustment.
- Verify vertical alignment using spirit level or plumb bob.
- Tighten anchor bolts to specified torque (refer to structural drawings).
- Apply non-shrink grout under base plates.
- Allow grout to cure before installing secondary members.
- Check alignment of post array using string line or laser level.
- Install primary beams (purlins) connecting the vertical posts.
- Attach secondary rails for module mounting.
- Ensure proper alignment and spacing as per drawings.
- Install bracing members for lateral stability.
- Tighten all fasteners to specified torque values.
- Verify tilt angle using digital inclinometer (tolerance: ±1°).
- Install end caps and safety features.
Fastener Type |
Torque Specification |
Installation Note |
M10 Grade 8.8 |
40-45 Nm |
Use calibrated torque wrench |
M12 Grade 8.8 |
70-75 Nm |
Apply anti-seize compound |
M16 Grade 8.8 |
170-180 Nm |
Double-check with secondary wrench |
M20 Grade 8.8 |
330-350 Nm |
Use tension control bolts where specified |
IS Code Reference: All bolted connections must comply with IS 4000:1992 "Code of practice for High Strength Bolts in Steel Structures."
Proper handling and preparation of modules is essential to prevent damage and ensure warranty validity.
- Inspect modules for damage before installation.
- Verify module type and serial numbers against delivery documentation.
- Pre-install module clamps or hardware if required.
- Clean module frame contact areas.
- Sort modules by power rating if mixing is unavoidable.
- Transport modules to mounting location with proper handling equipment.
- Position modules according to string layout diagram.
- Install mid-clamps between adjacent modules.
- Install end-clamps at array edges.
- Tighten clamps to manufacturer's torque specification (typically 12-15 Nm).
- Maintain proper gap between modules (typically 10-20mm).
- Verify mounting hardware is not shading any cell areas.
- Check for proper drainage channels between modules.
Proper alignment ensures optimal aesthetics, performance, and reduces stress on mounting components.
- Verify module rows are parallel (tolerance: ±5mm over 10m).
- Check module edges are flush with each other (tolerance: ±3mm).
- Confirm consistent gap spacing between all modules.
- Verify module tilt angle matches design specifications (tolerance: ±1°).
- Ensure all modules are secure by conducting random pull tests.
- Document module serial numbers and their locations in the array.
Safety Note: All module clamps must be installed and torqued properly. Improperly secured modules can become projectiles in high winds, causing property damage or injuries.
Proper grounding is essential for electrical safety and protection against lightning strikes.
- Follow IS 3043:2018 "Code of Practice for Earthing" requirements.
- Install earth electrodes at specified locations (typically array corners and every 30m).
- Connect all mounting structure components to the earthing system.
- Ensure module frames are properly bonded to the mounting structure.
- Verify earth resistance is below specified threshold (typically <5 ohms).
- Document earth resistance measurements for each electrode.
- Install air terminals (lightning rods) at specified height above arrays.
- Position air terminals to create proper protection zones (as per IS 2309).
- Connect down conductors from air terminals to dedicated earth pits.
- Maintain safe separation distance between lightning protection and DC circuits.
- Install surge protection devices at combiner boxes and inverters.
- Create equipotential bonding between different grounding systems.
- Use proper lugs and clamps certified for outdoor use.
- Apply anti-oxidation compound at all connection points.
- Secure grounding wire to structure at maximum 2m intervals.
- Use minimum 6mm² copper wire for module-to-rail bonding.
- Use minimum 16mm² copper for main earthing conductors.
- Verify continuity between all grounded components.
Test |
Acceptance Criteria |
Frequency |
Earth Resistance |
<5 ohms |
Each electrode |
Continuity Test |
<0.2 ohms between components |
10% of connections (min 5) |
Insulation Resistance |
>1 MΩ between live parts and ground |
Each string |
Proper cable selection is essential for system performance and longevity.
- Use solar-specific cables with UV resistance.
- Verify compliance with IS 7098 for power cables.
- Minimum cable specifications: 1000V/1500V DC rating, double insulated.
- Size cables for maximum 1% voltage drop.
- Select appropriate temperature rating (typically 90°C minimum).
- Route module cables along mounting rails using certified clips.
- Maintain minimum bending radius (typically 10x cable diameter).
- Protect cables from sharp edges with grommets or edge protection.
- Group and secure cables at maximum 60cm intervals.
- Use UV-resistant cable ties or metal clips for securing.
- Install cables to prevent water accumulation points.
- Provide drip loops at all connection points.
- Mount combiner boxes securely to mounting structure.
- Position boxes for easy access and maintenance.
- Install underground conduit for trunk cables.
- Bury conduits at minimum 600mm depth with warning tape.
- Provide expansion joints in long conduit runs.
- Seal all conduit entries with appropriate fittings.
- Label all cables and terminations per system diagram.
Critical Check: Ensure all module connector mating is complete with audible "click." Incomplete connections can cause arcing and fire hazards.
- Verify all mounting hardware is secured to proper torque.
- Check for any missing or loose fasteners.
- Confirm modules are clean and free from construction debris.
- Verify all cable connections are complete and secure.
- Conduct visual inspection for any damage to modules or structure.
- Check for proper grounding continuity.
- Document any deviations from design specifications.
- Measure open-circuit voltage (Voc) of each string.
- Verify string polarity is correct.
- Conduct insulation resistance test between positive/negative and ground.
- Measure earth resistance at multiple points.
- Verify DC and AC disconnect functionality.
- Test surge protection devices if installed.
- Document all electrical test results.
Proper documentation is essential for system warranty, operation, and maintenance.
- Prepare as-built drawings showing final installation details.
- Document module serial numbers and their locations.
- Compile all material test certificates and warranties.
- Prepare commissioning test reports.
- Create operation and maintenance manual.
- Provide emergency response procedures.
- Conduct handover training with client personnel.
- Foundation: Location, level, anchor bolt projection.
- Structure: Material grade, galvanization, alignment.
- Fasteners: Grade, torque verification, locking mechanism.
- Modules: Spacing, alignment, clamping.
- Grounding: Continuity, resistance values, connections.
- Cables: Routing, support, terminations.
- Always wear appropriate PPE (helmet, gloves, safety shoes).
- Use fall protection when working at heights (>2m).
- Handle solar modules with care to prevent glass breakage.
- Use proper lifting techniques and equipment.
- Verify electrical isolation before cable connections.
- Protect against arc flash hazards.
- Conduct daily toolbox meetings to review safety procedures.
Effective On-Job Training (OJT) is crucial for developing skilled personnel and ensuring high-quality installation practices.
- Structured Curriculum: Follow a predefined OJT plan covering all installation steps.
- Experienced Mentors: Assign experienced supervisors or technicians as mentors for trainees.
- Hands-on Practice: Provide ample opportunities for practical application of theoretical knowledge.
- Regular Feedback: Conduct daily or weekly feedback sessions to review performance and address gaps.
- Safety Integration: Emphasize and enforce safety protocols during all training activities.
- Tool Proficiency: Ensure trainees are proficient in using all relevant tools and equipment safely.
- Troubleshooting Skills: Train on identifying and resolving common installation issues.
- Documentation & Reporting: Teach proper documentation of work, quality checks, and daily progress.
- Performance Evaluation: Implement a system for evaluating trainee progress and competence.
- Continuous Improvement: Encourage a culture of continuous learning and adaptation to new technologies/methods.
Supervisor's Role: A good OJT supervisor acts as a guide, providing clear instructions, demonstrating best practices, and offering constructive criticism to foster skill development and adherence to quality standards.
Code Number |
Title |
Application |
IS 800:2007 |
Code of Practice for General Construction in Steel |
Structural design requirements |
IS 875 (Part 3) |
Design Loads (Wind Loads) |
Wind load calculations |
IS 1893 |
Criteria for Earthquake Resistant Design |
Seismic design requirements |
IS 4759 |
Hot-dip Zinc Coatings on Structural Steel |
Galvanization specifications |
IS 3043:2018 |
Code of Practice for Earthing |
Grounding system design |
IS 2309 |
Protection of Buildings from Lightning |
Lightning protection system |
IS 7098 |
Cross-linked Polyethylene Insulated Cables |
Cable specifications |
IS 2062 |
Hot Rolled Steel - General Structural Quality |
Material specifications |
Ground-mounted solar module mounting systems form the structural backbone of utility-scale PV installations. Following proper procedures for site assessment, foundation installation, structural assembly, and module mounting ensures a safe, durable system that will operate reliably for 25+ years.
Quality control at each stage of installation is critical, as correcting defects after completion can be extremely difficult and costly. Regular inspections, proper documentation, and strict adherence to IS codes and manufacturer specifications are essential for successful project execution.
Ongoing maintenance of the mounting system, including periodic structural inspections, torque verification, and corrosion monitoring, will help maintain system integrity throughout its operational life.
Key Takeaway: A robust MMS installation is key to maximizing energy yield and ensuring the long-term reliability of a solar PV plant.